Presentation of the AWHP-19APAT-R2B1: Efficiency and sustainability redefined.
Discover a new era of thermal efficiency with the AWHP-19APAT-R2B1. This heat pump is the product of careful research and development, designed to minimise energy costs and reduce the environmental footprint. Equipped with a sophisticated Twin Rotary compressor, it achieves impressive COP and EER values that guarantee resource-saving heating and cooling performance. AWHP-19APAT-R2B1 is a milestone for energy-efficient living and a smart choice for the environmentally conscious consumer.
With the AWHP-19APAT-R2B1, you are investing in a future in which energy efficiency and environmental protection go hand in hand.
€ 13,166 plus VAT.
Energy efficiency that sets standards The AWHP-19APAT-R2B1 heat pump from Airwende Umwelttechnik GmbH is a prime example of efficiency and sustainability. With outstanding COP values of up to 4.38 in heating mode, you make optimum use of every kilowatt hour and save energy costs.
Adaptability in any environment Thanks to its wide range of applications at outdoor temperatures from -25 to +43 °C, the AWHP-19APAT-R2B1 is your reliable partner all year round. It defies all weathers and ensures pleasant temperatures in your premises.
Environmentally friendly coolant for a green future With R32 as a refrigerant, you are choosing an environmentally conscious option. This refrigerant has a low global warming potential and therefore contributes to a responsible approach to our planet.
Performance that convinces Whether heating or cooling - with maximum outputs of up to 19.3 kW in cooling mode and 18.5 kW in heating mode, the heat pump offers generous capacities for use in residential and commercial buildings.
Discreet and quiet With a noise level of just 44 dB(A) inside and 57 dB(A) outside, the AWHP-19APAT-R2B1 operates whisper-quietly and unobtrusively in the background - your comfort takes centre stage, without any annoying background noise.
Intelligent design for easy integration The compact and well thought-out design enables uncomplicated installation and maintenance. This means less effort for you and more time to enjoy the newfound cosiness.
The AWHP-19APAT-R2B1 from Airwende Umwelttechnik GmbH not only stands for quality and efficiency, but also for the respectful use of natural resources - a genuine investment in a sustainable future.
Article no. | AWHP-19APAT-R2B1 | |
Refrigerant (type / quantity) | R32 / 3.0 kg | |
Max. heat output (DB 7°C / WB 6°C) | 18.5 kW | |
Power supply / frequency | 380 - 420 V / 50 Hz | |
Noise level | Indoor unit | 44 dB (A) |
Outdoor unit | 57 dB (A) |
Ambient temperature (DB/WB): 7/6 ℃ Water temperature (on/off): 30/35 ℃ | ||
C.O.P | 4.38 W/W | |
Ambient temperature (DB/WB): 7/6 ℃ Water temperature (on/off): 40/45 ℃ | ||
C.O.P | 3.58 W/W |
Ambient temperature (DB/WB): 35/24 ℃ Water temperature (on/off): 23/18 ℃ | ||
E.E.R | 3.05 W/W |
Ambient temperature | -25~43 ℃ | |
Minimum system water temperature (heating/cooling) | 20/7 ℃ | |
Tank volume | 250 L |
General technical data | |
---|---|
Device name | AWHP-19APAT-R2B1 |
Power supply | 380-420V / 50Hz |
Refrigerant | R32 |
Heat output under conditions (1) | |
Water inlet/outlet temperature 30°C/35°C | |
Ambient temperature DB 7°C/WB 6°C | |
Maximum heat output | 18.5 kW |
Coefficient of performance (COP) | 4,38 |
Heat output min./max. | 9.1/18.5 kW |
Heating power Input power min./max. | 1900/4200 W |
Coefficient of performance min./max. (COP min./max.) | 4,38/4,79 |
Heat output under conditions (2) | |
Water inlet/outlet temperature 40°C/45°C | |
Ambient temperature DB 7°C/WB 6°C | |
Maximum heat output | 18.2 kW |
Coefficient of performance (COP) | 3,58 |
Heat output min./max. | 8.5/18.2 kW |
Heating power Input power min./max. | 2300/5000 W |
Coefficient of performance min./max. (COP min./max.) | 3,58/3,72 |
Cooling capacity under conditions (3) | |
Water inlet/outlet temperature 23°C/18°C | |
Ambient temperature DB 35°C/WB 24°C | |
Maximum cooling capacity | 19.3 kW |
Energy efficiency ratio (EER) | 3,05 |
Cooling capacity min./max. | 16/19.3 kW |
Cooling capacity Input power min./max. | 4700/6300 W |
Energy efficiency ratio min./max. (EER min./max.) | 3,05/3,41 |
Cooling capacity under conditions (4) | |
Water inlet/outlet temperature 12°C/7°C | |
Ambient temperature DB 35°C/WB 24°C | |
Maximum cooling capacity | 15.8 kW |
Energy efficiency ratio (EER) | 2,89 |
Cooling capacity min./max. | 12.3/15.8 kW |
Cooling capacity Input power min./max. | 4000/5400 W |
Energy efficiency ratio min./max. (EER min./max.) | 2,89/3,04 |
Ambient conditions and installation | |
Operating range Ambient temperature | -25 to +43 °C |
Minimum ambient temperature (heating/cooling) | 20/7 °C |
Minimal space for installation, operation and storage | 6,2 m² |
Minimum pipework size | 6,2 m² |
Operating pressure | |
Maximum operating pressure High pressure | 4.2 MPa |
Maximum operating pressure Low pressure | 1.2 MPa |
Compressor and refrigerant | |
Compressor type | Twin Rotary |
Number of compressors | 1 |
Refrigerant type / quantity | R32 / 3 kg |
Fan system | |
Number of fans | 2 |
Air flow | 6200 m³/h |
Fan performance | 90 W |
Noise development | |
Noise level inside/outside | 44/57 dB(A) |
Heat exchanger | |
Heat exchanger type | Plate heat exchanger |
Water-side pressure drop | 26 kPa |
Water connections | |
Connections for water pipes | G5/4" |